C-Gate 1.5.1.3 build 1099
Release Notes
20031020

Changes in build 1099 (1.5.1.3)

1099/1 [enh#274] fixed wrongly represented group and terminal levels in C-Bus 2 input units after a psync operation.
1099/2 [enh#978] supports the RELDC4 changeover relay


Change in build 1098 (1.5.1.2)

1098/1 [enh#266] support added for SENPILL and SENPILLS unit

1098/2 [bug#265] fixed bugs relating to retrieving groups correctly across a bridged network

1098/3 [bug#254] fixed failure to recognise SENPIRSS v1.0


Changes in build 1096 (1.5.1.1)

1096/1 [bug#259] fixed incorrect reporting of terminal levels for CBus2 relays and dimmers


Changes in build 1095 (1.5.1.0)

1095/1 [enh#244] Added Support added for the following unit types: - ANODN4 (catalog L5504AMP) - RELMB8 - ANOMB8 - DSIMB8 and DIMDS8 (adds parameters specific to DSI units) - DIMPR12 (adds full unit model)


Changes in build 1093 (1.5.0.7)

1093/1 [bug#242] fixed problem that caused a Neo unit with a $FF application to cause a null pointer exception

Changes in build 1092 (1.5.0.6)1092/1  [enh#234] Added support for RELDN8SP1092/2	[enh#235] cbusunit.spe support for CBus2 SENPIRs1092/3	[enh#236] support for SENPILL added to cbusunit.spe (emulated as Neo unit)Changes in build 1091 (1.5.0.5)1091/1	[bug#220] Fixed problem where any network response received between a command 		being sent and a confirmation being received from the network results in the 		command being aborted with a 408 Error.1091/2	[enh#221] Set the default maximum missed responses (ie confirms for commands sent		through a PCI v3 or later to 5, and expose it as a parameter called max-missed-responses.Changes in build 10891089/1	[enh#183] Added support for RELDN8 unit.1089/2  [bug#184] Improved network exception handling for measurement and other application messages1089/3	[] Incorporate changes in build 1088 (cbusunit.spe) into core development tree.Changes in build 10881088/1  [cis#?] Updated cbusunit.spe to support CBus2 versions of DINAUX4 and KEYAUX4.Changes in build 10871087/1	[enh#169] Added support for General Input unit and measurement application mapped to		application $0F.  See the included PDF Document "Measurement in C-Gate 1.5" for details.1087/2	[bug#94] Removed dependency on PC_LOCAL in network unravel code which would have 		caused unravel failure with new PCIs1087/3	[bug#168] Fixed problem where extra '00' added to bridged commandsChanges in build 10861086/1	[bug#90] Removed problem resulting in frequent stuck -transmitter problems		due to misapplication of a confirm code to a '||' command.1086/2	[bug#91] Fixed problem with CBus2Unit model that was preventing visibility to		network voltages via CI command (and C-Lution)1086/3	[enh#92] Added new cbusunit.spe entries for CBus2 KEYIR4 unit1086/4	[enh#100] Added new entries for PCI V4 to cbusunit.speChanges in build 10851085/1	[bug#86] C-Gate -was- allowing on, off and ramp commands to return ok responses even 		if the network was disconnected.  This has been fixed, and a 408 Operation Failed		response is now returned in such a situation.1085/2	[bug#87] The bus coupler device was defined incorrectly in the unit specification, resulting		in target levels not being read correctly. This has been rectified.1085/3	[enh#88] New unit specifications have been added for the Reflection series of switches.1085/4	[enh#89] Support for automatic network reconnection on error/network or power failure.  All		types of network will attempt to reconnect if there are send or receive failures, or no response		is given to synchronisation operations or commands sent to the network.1085/5	[enh#89] The auto-reopen flag now defaults to "yes", rather than "no".  This means that networks		will attempt to reconnect if there is a significant interface error.Changes in build 10841084/1	[enh#60] C-Gate will no longer set $30 in a V4 Bridge in order to turn on monitoring. This 		is now the responsibility of the installer.1084/2	[enh#60] C-Gate now handles monitoring from bridges more than 1 level away, as long as the		bridge is configured correctly.1084/3	[bug#50] C-Gate has been modified so it will only search for up to 5 C-Gate hardware keys		and 5 C-Lution keys before giving up.  This is a workaround for the situation where bad or 		broken Sentinel software or PC hardware reponsts that an endless number of keys are available.		**Note this has created a limitation: a maximum of 5 dongles of each kind		are supported.**Changes in build 1083:1083/1	[bug#15] Fixed null pointer exception resulting from get <terminal> groups for din/pro units.Changes in build 1082:1082/1  [xc0008] Changed to release versionChanges in build 1081:1081/1	[xc0007] Fixed potential bad or confusing responses issued by the CI command		